RPS-500 Analog Ranging Card
CLICK HERE to download a
catalog sheet for this product.
- Analog
Ranging Card
- 2500
Volts Isolation
- 1 - 10
VDC Analog Voltage
- 4 - 20 mA Analog
Current
- Ranges
2"-14", 5"-36", 5"-72",10"-240"
- Inverting
Switch
- Zero,
Span, Sample & Hold Controls
- 120VAC or
24VDC Power Input
|
 |
The RPS-500
ranging board was designed to give analog voltage
and current outputs proportional to distance and
can be used with the RPS-100, RPS-300, RPS-325 or
RPS-326. It is a fast, accurate means of
converting analog pulse width generated by the
ultrasonic sensor into analog voltage and current.
Ranges available are 2" to14", 5" to 36", 5" to
72", 10" to 240".
ZERO & SPAN CONTROLS
The RPS-500
analog card comes with a zero and span control.
These two potentiometers allow the analog signal
to be adjusted over a desired range. The
adjustment ratio is 5:1. This means that the
RPS-500-14 (range 2" to 14") can be adjusted to
give an analog output over a range as small as
2.4" or as large as 12". Example: If you desired a
4mA signal at 4" and a 20mA signal at 14" you
would adjust the analog card as follows. Place a
target at 4" and adjust the zero control until
your current meter reads 4mA. Move the target to
14" and adjust the span control until you reach
20mA. With no more than two adjustments of each
potentiometer the desired range will be achieved.
If the analog card is in the inverted state,
voltage and current decreasing with distance, the
zero pot will adjust the 20mA point and the span
pot will adjust the 4mA point. Always adjust the
close point first.
INVERTING ANALOG SIGNALS
Both the current
and voltage outputs of the analog RPS-500 card can
be inverted. In the non-inverted state (switch 1
ON switch 2 ON) the voltage and current increase
with distance. In the inverted state ( switch 1
OFF switch 2 OFF) the voltage and current decrease
with distance. Note: The inverting switches should
be set in the desired positions before beginning
adjustments with the zero and span controls.
SAMPLE AND HOLD
After each
return echo the output voltage and current are
updated. If no echo is received the previous
readings are maintained or held. The time these
readings are maintained will depend on the setting
of the hold potentiometer, cw (up to 5 seconds).
After this time has elapsed, the outputs will go
to there maximum readings, indicating that there
is no return echo. The advantage of this control
is that it allows an echo or echos to be missed
for a time without changing the output readings.
This has proven to be advantageous in level
control where the surface may be agitated.
LED DISPLAY
This 10 segment
LED display will tell when a return echo is in the
range of the sensor. For example, when the RPS-500
card is used with the RPS-300-14 and the target is
4 inches away just 1 or 2 LEDs will be on. When
the target moves to 9 inches about 1/2 of the
display will be on, and when the target is 14"
away all the LEDs will be on.
ENABLE LINE
When the enable
line is held high (high = 3 to 30V) the sensors
will not transmit and the hold circuit will time
out, causing the outputs to go to a maximum
reading. A short time (Approximately 4.2mS) after
the enable line is pulled low (low = 0 to 1V) the
sensors will transmit. When a return echo is
received the outputs will be updapted.
|
Specifications: |
RPS-500 |
|
|
Power Input: |
120 VAC or 24 VDC |
|
Ambient Temperature: |
0ºC to 60ºC or 32ºF to 140ºF |
|
Output 4 - 20mA: |
Current sourcing, load 0 to 500
ohms. Reference to "GND OUT" terminal. |
|
Output 0 - 10VDC: |
Load Equal to or Greater than
500 ohms. Reference to "GND OUT" terminal. |
|
Up Date Time: |
10mS 14" card, 20ms 36" card,
40mS 72" card, 150mS 240" card. |
|
ZERO Control: |
Adjustable |
|
SPAN Control: |
Adjustable 5 : 1 ratio. |
|
Switches: |
1 ON, 2 ON increase voltage and
current with distance.
1 OFF, 2 OFF decrease voltage and current with
distance. |
|
Output Isolation: |
2500V for outputs 0-10 VDC,
4-20MA when powered by 120 VAC. |
|
Using the RPS-500: |
The distance control on the
front cover of the control box
must be full cw for maximum analog ranges.
The supplied cable is used to connect the
RPS-500 board
to the RPS-100, 300, 325, or 326 Ultrasonic
Sensor.
This cable has shielding between "XMIT" and
"1st DET"
which is needed to prevent cross talk.
The following wire connections should be made.
|
RPS-100, 300, 325, 326
GND
+12VDC
XMIT
1st DET. |
Cable Wire Color
BLACK
WHITE
RED
GREEN |
RPS-500
GNC
+12VDC
XMIT
1st DET. |
 |
| Figure: |
|
|
|
A-Wiring Diag.
- For RPS-100, 300, 325, 326
B-Wiring Diag. - For RPS-500 |
|
| PART NUMBER
|
RANGE
|
OUTPUT
|
RPS-500-14
RPS-500-36
RPS-500-72
RPS-500-240 |
2" - 14"
5" - 36"
5" - 72"
10" - 240" |
Analog 0 -10
volt, 4 - 20mA, Inverted or non-inverted
Analog 0 -10 volt, 4 - 20mA, Inverted or
non-inverted
Analog 0 -10 volt, 4 - 20mA, Inverted or
non-inverted
Analog 0 -10 volt, 4 - 20mA, Inverted or
non-inverted |
|